General
The 30-3013 Explosion Proof Smoke Detector has Division and Zone explosion-proof ratings and is suitable for industrial and commercial applications. The detector is designed to operate effectively with smoldering and rapidly growing fires and contains the ability to annunciate fault ensuring no undis- closed failures. The 30-3013 Smoke Detector outputs include 0-20 mA, a localized LED, and relays.
DN-60911:A
Features
IECEx Zone approved
Trouble-free photoelectric operation
0-20 mA output for DCS integration
Self-checking circuitry ensures reliable smoke detection
Alarm, Auxiliary and Fault relays for controlling annunciat- ing devices or fire panel interface
LED provides a visual indication that an alarm has occurred
IP44 ingress protection level suitable for onshore or off- shore requirements
Ideally suited for classified areas in the petrochemical, oil and gas industry
DCS, PLC, integration with milliamp or relay outputs
Rugged design for environmental extremes
Visual confirmation of detector alarm
Detects smoldering fires
No undisclosed failures
Applications
Combustible storage facilities
Munitions manufacturing
Volatile chemical storage
Chemical processing plants
Petroleum refineries
Turbine enclosures
Battery rooms
HVAC applications
The hot-swappable sensor module is intrinsically safe and allows live maintenance while under power, without de-classi- fying the hazardous area. The integrated junction box is avail- able in a variety of port configurations for simplified wiring and installation.
Certifications
FM Approved
Class 1 Div 1 Groups B, C. D T4
Class 1 Div 2 Groups A, B, C, D, T4
Class 1 Zone1 AWX db ia llC T4 Gb IEC/IECx
FMG 15.0014X
Ex db ia llC T4 Gb
Specifications
Power Consumption 3.5 watts maximum (2.75 watts at 24 VDC)
Output Relays
Smoke alarm relay, Form C, 5 amperes at 30 VDC. The smoke alarm relay has normally open/normally closed con- tacts and normally de-energized operation.
Fault relay, Form A, 5 amperes at 30 VDC.The fault relay has normally open contacts and normally energized opera- tion.
Auxiliary relay, Form C, 5 amperes at 30 VDC. The auxiliary relay has normally open/normally closed contacts and nor- mally de-energized operation.
Temperature Range
Operating: –20°C to 65°C (–4°F to 149°F)
Storage: –55°C to 70°C (–67°F to 158°F)
Humidity Range 5 to 95% relative humidity.
Ingress Protection IP44 (Applicable to ceiling mount only).
Current Output 0-20 mA (±0.3 mA) DC current, with maxi- mum loop resistance of 300 ohms from 12-17.9 VDC, 500 ohms from 18 to 19.9 VDC, and 600 ohms from 20-30 VDC.
Terminals UL/CSA rated for 14-18 AWG or 2.5-0.75 mm2 wire.
Thread Options 3/4 inch NPT or M25. Multi-port models avail- able.
Enclosure Material Polycarbonate / ABS - Smoke Detector. Copper-free aluminum (painted) - Junction Box.
Shipping Weight (Approximate) 7.85 lbs (3.56 kg).